CAN Repeater CRep S4

CAN Repeater CRep S4

is a CAN repeater with 4 channels, which transmits and amplifies signals transparent to the CAN protocol.

Special Features

CAN Repeater CRep S4

  • Protocol transparent CAN repeater
  • 4 CAN channels
  • Low propagation delay
  • ISO 11898 compatible bus interface
  • Detach of dominant locked bus segments
  • Rail mountable

Description

The compact CAN repeater CRep S4 transmits and amplifies signals transparent to the CAN protocol. Each of the four CAN connections has the physical behavior of a single bus node. CRep S4 permits a flexible design of the network topology and offers special support for star structured networks. Furthermore tree structures and long stub lines are supported. Through the possibility to use the network structure that fits the application best a reduction of installation costs can be reached.The maximum data rate in CAN networks, depending on signal propagation delays, can be increased, if CRep S4 is used to improve the network structure. An increase of the maximum node count in a CAN network can be reached by splitting the network in subnets that are connected by CRep S4. Each subnet makes the number of CAN nodes possible permitted by the drivers output current. Where CAN signals have to be transmitted over long distances, CRep S4 can be used for signal conditioning. The capability to detach erroneous segments from the rest of the CAN system reduces the impact on the intact bus segments for the most commonly occurring errors.The presence of power is indicated by a LED. Furthermore each CAN channel is provided with a LED indicating that this channel has originated a CAN message when the LED is on.

Ordering information

Equipment / Variants

12-06-002-10

CRep S4-05/S24/RMD

Galvanic separation: None

Number of channels: 4 Channel

CAN Physics: high speed

Protocol: CAN

Protocol: CANopen

Structural shape: Mounting rail

Inhibit time: 500 ns

For baud rate: 500 kB/s

For baud rate: 250 kB/s

12-06-003-10

CRep S4-10/S24/RMD

Galvanic separation: None

Number of channels: 4 Channel

CAN Physics: high speed

Protocol: CAN

Protocol: CANopen

Structural shape: Mounting rail

Inhibit time: 1000 ns

For baud rate: 125 kB/s

12-06-004-10

CRep S4-20/S24/RMD

Galvanic separation: None

Number of channels: 4 Channel

CAN Physics: high speed

Protocol: CAN

Protocol: CANopen

Structural shape: Mounting rail

Inhibit time: 2000 ns

For baud rate: 50 kB/s

12-06-005-10

CRep S4-50/S24/RMD

Galvanic separation: None

Number of channels: 4 Channel

CAN Physics: high speed

Protocol: CAN

Protocol: CANopen

Structural shape: Mounting rail

Inhibit time: 5000 ns

For baud rate: 20 kB/s

12-06-006-10

CRep S4-100/S24/RMD

Galvanic separation: None

Number of channels: 4 Channel

CAN Physics: high speed

Protocol: CAN

Protocol: CANopen

Structural shape: Mounting rail

Inhibit time: 10000 ns

For baud rate: 10 kB/s

0

Technical Data

Layout and Connection

A CRep S4 device includes four CAN segments, wired by terminal blocks with 3 clamps. The power supply of CRep S4 is separately wired by a terminal block with 2 clamps.

PinNameFunction
1CAN_HCAN high bus line
2CAN_LCAN low bus line
3GNDGround

The following table shows the terminal assignment of the power connector:

PinNameFunction
1Power +Positive supply +24 V
2Power –Ground

The power supply is galvanicly decoupled from the CAN system.

Limiting Values

ParameterMinimumMaximumUnit
Storage temperature-40+80°C
Operating temperature0+60°C
Power supply voltage-100+35V
Voltage on signal lines-30+30V
Maximum power dissipation (at 60 °C)n.s.tbdmW

Any (also temporary) stress in excess of the limiting values may cause permanent damage on CRep S4 and other connected devices. Exposure to limiting conditions for extended periods may affect the reliability and shorten the life cycle of the device.

Nominal Values

ParameterMinimalTypicalMaximalUnit
Current consumption (running idle)n.s.26n.s.mA
Current consumption (250 kBits/s, 100 % busload)n.s.65n.s.mA
Supply voltage192430V
Propagation delay between two arbitrary channelsn.s.130200ns

All values, unless otherwise specified, refer to a supply voltage of 24 V and an environmental temperature of 20 °C.

Scope of Delivery

  • CAN repeater CRep S4
  • User manual

Related Products

CAN Repeater CRep S8C

CAN Repeater CRep S10I

CAN Repeater CRep N

CAN Repeater CRep Opto

Further Information

CAN Repeater Example

CAN Repeater Networks

CAN Repeater Inhibit Time

International Sales

For US/Canada/Mexico sales, please contact: Traquair Data Systems, Inc. (www.traquair.com); sales@traquair.com; Ph: +1 607 266 6000