CAN Repeater CRep S4/FD
is CAN repeater with 4 channels and increased immunity to common-mode interference for Classic CAN and CAN FD
Special Features
CAN Repeater CRep S4/FD
• Protocol transparent CAN repeater for CAN FD and CC
• 4 CAN channels
• Low propagation delay
• ISO 11898-2:2016 and CiA 601-4 (SIC) compatible bus interface (TI TCAN1462)
• Detach of dominant locked bus segments
• Signal conditioning over long distances
Description
The DIN rail-mountable CAN repeater CRep S4/FD was developed with signal quality in mind. The use of a Signal Improvement Capability Transceiver (SIC) for the physical CAN interface and split termination enables stable signal transmission and increased immunity to common-mode interference for Classic CAN and CAN FD.Each of the four CAN channels physically behaves like a single bus node. CRep S4/FD enables the implementation of star network structures. This opens up the possibility to select a network topology, that can help to reduce installation costs.The ability to isolate permanent dominant segments from the rest of the CAN system after an error time reduces the impact of the most frequently occurring errors on intact bus segments. CRep S4/FD features split termination with 2 x 60 ohms. If termination isn't required, the device is offered with high-ohm resistors to ensure that a channel without a connected or unterminated cable cannot interfere with the rest of the network.The operating voltage is indicated by an LED. Each channel is also assigned an LED to indicate which segment has generated a CAN message.Ordering information
Equipment / Variants
12-50-002-20
CRepS4/FD-5/S24/RMD
For baud rate: 500 kB/s
For baud rate: 250 kB/s
Inhibit time: 500 ns
Termination: No Termination
Galvanic separation: None
Number of channels: 4 Channel
Protocol: CAN
Protocol: CANopen
Protocol: CAN FD
Structural shape: Mounting rail
12-50-102-20
CRepS4/FD-5/S24/RMD
For baud rate: 500 kB/s
For baud rate: 250 kB/s
Inhibit time: 500 ns
Termination: 120 Ohm
Galvanic separation: None
Number of channels: 4 Channel
Protocol: CAN
Protocol: CANopen
Protocol: CAN FD
Structural shape: Mounting rail
12-50-003-20
CRepS4/FD-10/S24/RMD
For baud rate: 125 kB/s
Inhibit time: 1000 ns
Termination: No Termination
Galvanic separation: None
Number of channels: 4 Channel
Protocol: CAN
Protocol: CANopen
Protocol: CAN FD
Structural shape: Mounting rail
12-50-103-20
CRepS4/FD-10/S24/RMD
For baud rate: 125 kB/s
Inhibit time: 1000 ns
Termination: 120 Ohm
Galvanic separation: None
Number of channels: 4 Channel
Protocol: CAN
Protocol: CANopen
Protocol: CAN FD
Structural shape: Mounting rail
12-50-004-20
CRepS4/FD-20/S24/RMD
For baud rate: 50 kB/s
Inhibit time: 2000 ns
Termination: No Termination
Galvanic separation: None
Number of channels: 4 Channel
Protocol: CAN
Protocol: CANopen
Protocol: CAN FD
Structural shape: Mounting rail
12-50-104-20
CRepS4/FD-20/S24/RMD
For baud rate: 50 kB/s
Inhibit time: 2000 ns
Termination: 120 Ohm
Galvanic separation: None
Number of channels: 4 Channel
Protocol: CAN
Protocol: CANopen
Protocol: CAN FD
Structural shape: Mounting rail
Technical Data
Layout and Connection
CRep S4/FD includes four CAN segments, wired by terminal blocks with 3 clamps. The power supply of CRep S4/FD is separately wired by a terminal block with 2 clamps. The following table shows the terminal assignment of the power supply
The following table shows the terminal assignment of the power connector:
| Pin | Name | Function |
| 1 | Power + | Supply voltage |
| 2 | Power – | Ground |
The following table shows the pin assignment of the CAN terminal block:
| Pin | Name | Function |
| 1 | CAN_H | CAN data line (dominant high) |
| 2 | CAN_L | CAN data line (dominant low) |
| 3 | CAN_GND | CAN ground |
Limiting Values
| Parameter | Minimum | Maximum | Unit |
| Storage temperature | -40 | +85 | °C |
| Operating temperature | -20 | +70 | °C |
| Power supply voltage | -100 | +35 | V |
Any (also temporary) stress in excess of the limiting values may cause permanent damage on CRep S4/FD and other connected devices. Exposure to limiting conditions for extended periods may affect the reliability and shorten the life cycle of the device.
Nominal Values
| Parameter | Minimal | Typical | Maximal | Unit |
| Current consumption (running idle) | – | 26 | – | mA |
| Current consumption (250 kBits/s, 100 % busload) | – | 65 | – | mA |
| Supply voltage | 19 | 24 | 30 | V |
| Propagation delay between two arbitrary channels | – | 130 | 200 | n.s. |
All values, unless otherwise specified, refer to a supply voltage of 24 V and an environmental temperature of 20°C.
Scope of Delivery
• CAN repeater CRep S4/FD
• User manual